Description:
Intensity of Remote Signalling Alarm Contact
Failure indication and centralized remote signalling alarm dry contacts;
High discharge capacity and low residual voltage;
Over-temperature protection;
IP20, UL94 V0
Model Number
SUP1
SPD according IEC 61643-1
Class II
SPD according EN 61643-11
Type 2
Operating Temperature Range
-40ºC~+80ºC
Relative Humidity
≤95%(25ºC)
Atmospheric Pressure
86~106kPa
Working Frequency
50/60Hz
Rated Working Voltage Uo
230V/400V~
Max Continuous Operating Voltage Uc(L-N)
275V/320V/385V/420V ~
Mode of protection
L-N/N-PE
Nominal Discharge Current In(8/20μs)(L-N)
20kA
Max Discharge Current Imax (8/20μs) (L-N)
40kA
Voltage Protection Level Up(L-N)
≤1.2kV
Max. mains-side Overcurrent Protection
80A(gL/gG)
Cross sectional area for wiring terminal connected to conductor
Stranded:4~25mm²
Solid Wire: 4~35mm²
Max. Cross-sectional Area For Remote Signaling Interface
1.5mm²
Torque: wiring terminal/remote signaling interface
2.5Nm
Enclosure material
PBTV-0
Degree of protection(IP code)
IP20
Mounting
DIN35mm rails
Solar DC SPD
The SUP series Surge Protection are designed to protect against lightning surge voltages in photovoltaic power supply networks.
These units must be installed in parallel on the DC networks to be protected and provide common and differential modes protection. The SUP series is available for the main operating voltages in photovoltaic: 1000 Vdc.
The use of SUP series Surge Protection is recommended at both ends of the DC power supply line (solar panel side and inverter/converter side),
Especially if the line routing is external and long. The electrical diagram of the SUN-S40 series is based on high energy PV equipped with specific thermal disconnectors and related failure indicators.
The SUP series is made with plug-in modules to allow a fast and easy maintenance in case of failure (disconnection from the DC network).
SUP2-PV series surge protector
SUP4-PV
PV DC specific (LEC 6614-1/EN 61643-11)
Pole
2 pole
3 pole
Electrical Parameter
Classifical test
II
II
Uoc max (V DC)
500
900
Uc (V DC)
500
1000
In(8/20)us (KA)
20
20
Imax(8/20)us (KA)
40
40
Up (KV)
2.0
3.8
Remote control and indication Indication window Plug-in module Remote signal contact
Remote signal contact
Max working volt
250V AC/30V DC
250V AC/30V DC
Max working amp 1A (250V/AC)
1A (250V/AC)
1A (250V/AC)
1A (30V DC)
1A (30V DC)
1A (30V DC)
Wiring & installation
Wiring capacity(mm2)
Hard wire
4-25
4-25
 Flexible wire
4-16
4-16
Stripping length
10
10
Terminal screwa
M5
M5
Torque(Nm)
Main ciruit
3.5
3.5
Remote signal contact
0.25
0.25
Protection class
All profile
IP40
IP40
Connection port
IP20
IP20
Installation environment
No obvious shock and vibration
Altitude(m)
≤ 2000
≤ 2000
Working temperature
-3.0--+70
-3.0--+70
Relative humidity
30%-90%
30%-90%
How to install
Install with H35-7.5/DIN35 stell mounting rail
Size(mm) (W*H*L)
W
36
54
H
90
90
L
67.6
67.6
Weight (KG)
0.25
0.38
Nominal PV system volt
600V
100V
1200V
MCOV(UCPV)
700V DC
1170V DC
1200V DC
Max system discharge Current (8/20us) (Imax)
40KA
40KA
30KA
Volt protection leve (UP)
≤ 2.5KV
≤ 4.0KV
≤ 4.5KV
Volt protection Level at 5KA (UP)
≤ 2.0KV
≤ 3.5KV
≤ 4.0KV
Integrate fuse breaking capacity/interrupting rating
30KA/1000V DC
30KA/1000V DC
30KA/1200V DC
Technology
Short-circuit interruption (SCI) overcurrent protection
Operating temperature range
-40 to +80
Nominal discharge current
12.5KA
Response time (ta)
<25ns
Operating state/fault indication
Green (good) / Red (replace)
Mounting
35mm DIN Rail per EN 60715
Degree protection
IP20
capacity
3 modules DIN 43880
Model NO.: SUP1
Shape: Cuboid
Material: Ceramic
Certification: ROHS, ISO9001, CCC, CE
Brand: Suntree/OEM
DC: 1000V 500V
AC: 275V 320V 385V 420V
Ka: 5ka-100ka
Certificate: CE
Protection Class: IP40
Operating Temperature: 5°c - +50°c
Poles: 1p 2p 3p 4p
Max Working Volt: 250V AC/30V DC
Hard Wire: 4-25
Flexible Wire: 4-16
Trademark: SUNTREE/oem
Specification: CE
Origin: Zhejiang China
HS Code: 853540000
AC 320V lightning surge protector 30-60KA 4 pole