Danfoss frequency converters have two methods to implement initialization, the first method:
1. Disconnect the main power and wait for the display to turn off.
2, during power up for LCP 102, press the [Status], [Main Menu], [OK] button.
3. Release these keys after 5 seconds.
4. The drive is now set to the default settings.
P 15-00 In addition to operating parameters time, frequency and power parameters P15-03, the parameter P 15-04 times over-temperature, over-frequency and voltage parameters P 15-05, the other parameters are set to the initialization.
The second initialization method:
1. Select parameter 14-22 working mode
2. Press [OK]
3. Select "Initialize"
4. Press [OK]
5. Turn off the main power and wait for the display to turn off.
6. Reconnect the main power.
In addition to protocol P8-30, P8-31 address, P8-32 FC Port Baud Rate, P8-35 minimum response delay, P8-36 maximum response delay, maximum byte delay between P8-37, P14-50 RFI filter , P15-00 runtime to 15-05 over Volt, P15-20 15-22 event records to a recording time, P15-30 error code to 15-32 alarm Log addition, other parameters are set to default values.

Network & Accessories

Networking Keystone Jacks, Punch Down Type Terminals.China Network & Accessories,Networking KEYSTONE Jacks supplier & manufacturer, offer low price, high quality Punch Down Type Terminals,, etc.

Networking KEYSTONE Jacks, Punch Down Type Terminals.China Network & Accessories,Networking KEYSTONE Jacks supplier & manufacturer, offer low price, high quality Punch Down Type Terminals,, etc.

Networking KEYSTONE Jacks, Punch Down Type Terminals.China Network & Accessories,Networking KEYSTONE Jacks supplier & manufacturer, offer low price, high quality Punch Down Type Terminals,, etc.

Network & Accessories,Networking KEYSTONE Jacks, Punch Down Type Terminals

ShenZhen Antenk Electronics Co,Ltd , https://www.atkconnectors.com