The synchronous generator test project is a test item for a synchronous generator with a capacity of 0.6 MW or more in the Pre-Regulation (for those below 0.6 MW), including turbo generators and hydro-generators. According to the requirements of the "pre-regulation", the following main test items should be carried out:

        1) measurement of insulation resistance, absorption ratio or polarization index of the stator winding;

        2) DC resistance measurement of the stator windings;

        3) stator winding leakage current and DC withstand voltage test;

        4) AC voltage withstand test of stator and rotor windings;

        5) Measurement of insulation resistance and DC resistance of the rotor winding;

        6) testing of equipment connected to the excitation circuit of the generator and exciter;

        7) Stator core test;

        8) Measurement of insulation resistance and shaft voltage of generator and exciter bearings;

        9) Rotor winding AC impedance and power loss test;

        10) Stator slot coil anti-halation layer to ground potential test;

        11) DC voltage measurement is applied to the end of the stator winding of the stator winding;

        12) Turbine generator stator winding end natural frequency test;

        13) Generator no-load and short-circuit test;

        14) Generator temperature rise test;

        15) Phase sequence checking and phasing.